ABB ACS600 Replacement and Upgrade Options
Request an ACS600 Upgrade Review
ABB has declared the air-cooled ABB ACS600 MultiDrive obsolete since January 1, 2025, and the ACS601 and ACS611 obsolete since January 1, 2014. SAF Drives replaces ACS600 drives with the ABB ACS880. Send a photo of the drive’s model number and the motor nameplate, tell us what the drive controls, and SAF will review your equipment and recommend the upgrade.
Is the ABB ACS600 still supported?
Only in a limited way. ABB lists the ACS600 family (written “ACS 600” in older ABB manuals) among its legacy drives, and its own lifecycle documents show these statuses:
- ACS600 MultiDrive (air-cooled): Obsolete since January 1, 2025. ABB recommends “to either do a Retrofit or to replace the ACS600 with a new product family.” Source: ABB lifecycle statement (PDF)
- ACS601 and ACS611: Obsolete since January 1, 2014. ABB states that in this phase it cannot guarantee services “within reasonable cost or technically.” Source: ABB lifecycle statement (PDF)
- ACS600 single drives: In a March 2022 brochure, ABB said ACS600 single drives “are at the Limited phase of their life cycle” and that ACS607 drives “are coming to the end of their life cycle.” Source: ABB modernization brochure (PDF)
ABB rates every product as Active, Classic, Limited or Obsolete. For the obsolete ACS600 MultiDrive, ABB’s own recommendation is a retrofit or a replacement.
What replaces the ABB ACS600?
SAF replaces every ABB ACS600 variant with the ABB ACS880, ABB’s current drive family. That includes ACS600 single drives and the ACS600 MultiDrive.
| ABB ACS600 variant | SAF’s recommended replacement |
|---|---|
| ABB ACS601 | ABB ACS880 |
| ABB ACS604 | ABB ACS880 |
| ABB ACS607 | ABB ACS880 |
| ABB ACS611 | ABB ACS880 |
| ABB ACS617 | ABB ACS880 |
| ABB ACS627 | ABB ACS880 |
| ABB ACS677 | ABB ACS880 |
| ABB ACS600 MultiDrive | ABB ACS880 |
Note: Every installation is different. SAF reviews the drive, motor and application before recommending the replacement.
Variant not listed? Send us a photo of the nameplate.
Also running older SAFTRONICS equipment? See SAFTRONICS legacy support and upgrades.
Should you repair, replace or upgrade an ACS600?
It mostly depends on how much time you have. If the equipment is down and you need a quick turnaround, a repair, replacement parts, or an available suitable replacement is usually the fastest option. If you have more time, a retrofit or upgrade is an option.
With more time, SAF can help you select a product your team already knows or has on other equipment. Many companies like to move toward a similar brand of product for ease of troubleshooting and spare parts.
What changes when you upgrade an ABB ACS600 to an ACS880?
The control wiring and the communication cards change. The power wiring may or may not.
- Control wiring will change.
- Communication cards will be ACS880-specific, so the communication cards from the ACS600 can’t be reused.
- Power wiring and connections may or may not have to change.
A communication card is the plug-in adapter that connects a drive to the plant’s control network. If your control system talks to the ACS600 over an outdated communication protocol, the PLCs and input/output cards may need to be upgraded alongside the drive. After the drive itself, communication networks and PLC processors are some of the most common things SAF upgrades when it overhauls a system.
Settings are the other big change. Legacy drives have been in service so long that they are often seen as “black boxes” that no one knows exactly how they work. Modern drives can be more complicated to program; their control algorithms may not match the legacy equipment; and their parameters and settings may be different. That can make copying the old ACS600 parameters to the ACS880 difficult or impossible, so the new drive may need to be set up from scratch.
How SAF handles an ACS600 upgrade
- Send your drive details. Take a photo of the model number on the ACS600 and of the motor nameplate, and tell SAF what the drive controls (for example, a fan, pump or rock crusher).
- SAF reviews and recommends. SAF reviews the information and recommends the ACS880 replacement for your equipment.
- Plan around your shutdown. SAF identifies which upgrades realistically fit your shutdown window, then pre-engineers the scope and sequencing.
- Build and test off-site. Where possible, SAF builds and tests the system before it reaches your site, which reduces commissioning surprises.
- Commission. SAF commissions the new drive with a focus on stability and repeatability.
SAF’s experience with ABB ACS600 drives
SAF was the first company to do shaftless drive control with ABB. Shaftless drive control synchronizes individual motors electronically instead of linking them with a mechanical line shaft.
Working closely with ABB, SAF developed custom firmware in the ACS600. SAF also developed its DDCS fibre optic connection between the SAFphire controller and the ACS600, then the ACS800 and now the ACS880. SAFphire is SAF’s programmable linear controller for closed-loop coordinated drive control.
That work gives SAF extensive application experience and history to draw from when upgrading ACS600 systems.
Is the ABB ACS800 obsolete?
Not yet. ABB lists the ACS800 R7–R8 single drives and drive modules (ACS800-02, -04 and -07, and their -U versions) in its Classic phase since July 1, 2017. ABB will move them to the Limited phase on January 1, 2030.
ABB also states that new modules for the ACS800-04, -U4 and -04(M) R7–R8 drive modules are available as spare parts until the second half of 2028, and that “spare part modules will not be available in the Limited phase.” Other ACS800 types have their own ABB lifecycle statements. Source: ABB ACS800 R7–R8 lifecycle announcement (PDF)
Frequently asked questions
Request an ACS600 upgrade review
Tell us the ACS600 model number, what the drive controls are, and whether you need help with a fault or a planned upgrade. Include a photo of the drive’s model number and the motor nameplate. Let us know if production is stopped or if you are planning work for a future shutdown.